E-15 · Interactive Lab
Valve Cv & authority
Pick the valve characteristic and drag the authority: watch the installed curve distort away from the inherent one as authority drops, and see why an oversized valve (low authority) gives poor, early-opening control.

Interactive valve sizing lab showing inherent versus installed characteristic as a function of valve authority.

inherent characteristic installed characteristic x: valve position · y: flow
0.50