Technical Trade SchoolBAS-300 service-series
BAS-311
Ten concept and evidence figures

BAS-311 Visual Aid Library

Figure-use rule

Each figure is an orientation and reasoning aid, not a project drawing. Learners must pair it with the current sequence, point list, wiring/piping documents, manufacturer instructions, and as-found evidence.

Figure 1 — Equipment identity and control-method overlays

Normal-rule anchor

The HVAC process is independent of whether the control signal is pneumatic, electric, electronic, or DDC; signal method changes the evidence path.

Case overlay

An older AHU uses pneumatic actuators with DDC EP transducers and a modern supervisor.

Calculation/evidence callout: Map percent command through 0–10 V or 4–20 mA to 3–15 psi and expected actuator direction using supplied ranges.

Figure 2 — Terminal VAV, fan-powered, and fan-coil units critical

Normal-rule anchor

Airflow value is trustworthy only when pickup, tubing, sensor, range, K-factor, density basis, and calibration are correct.

Case overlay

A VAV box reports design airflow with the damper closed and AHU fan off.

Calculation/evidence callout: Use supplied flow=K×√ΔP relationship and min/max/dual-maximum sequence to predict state and airflow target.

Figure 3 — VVT and hybrid measured-airflow VVT

Normal-rule anchor

Hybrid VVT can run on standard VAV controllers, but zone airflow measurement does not turn the central packaged source into a central VAV air handler.

Case overlay

Four zones vote for cooling while one perimeter zone needs heat and the bypass strategy is unstable.

Calculation/evidence callout: Calculate zone vote/priority, airflow target, crossflow pickup ΔP using supplied K, and central static/bypass response.

Figure 4 — Packaged RTU, SZVAV, and heat-pump sequences critical

Normal-rule anchor

BAS commands are subordinate to factory safeties and OEM refrigerant/compressor controls.

Case overlay

A heat pump enters defrost while the BAS trend appears to show simultaneous cooling and auxiliary heat.

Calculation/evidence callout: Calculate stage thresholds, delays, lockouts, supply-air targets, and expected mode from supplied sequence.

Figure 5 — VAV air-handling systems critical

Normal-rule anchor

Static and SAT resets respond to verified demand within limits; they do not excuse failed boxes, sensors, or protections.

Case overlay

Static pressure stays at maximum while many VAV dampers are nearly closed.

Calculation/evidence callout: Calculate mixed air, static/SAT reset, request response, fan speed estimates, and timing from the approved sequence.

Figure 6 — Ventilation, DOAS, VRF, and heat-recovery interfaces critical

Normal-rule anchor

VRF does not inherently provide required outdoor air; the DOAS/ventilation path and controls must be identified separately.

Case overlay

VRF zones are comfortable while CO2 rises because the DOAS is disabled by schedule.

Calculation/evidence callout: Calculate ventilation path timing, dew-point target, heat-recovery temperature effectiveness when supplied, and mode demand.

Figure 7 — Smoke, fire, and life-safety interface boundary critical

Normal-rule anchor

Ordinary HVAC optimization and operator commands never outrank approved smoke-control and fire-alarm functions.

Case overlay

A normal occupied command conflicts with an active smoke-control mode indication.

Calculation/evidence callout: Build a priority/state table from supplied approved documents; do not calculate or invent life-safety acceptance criteria.

Figure 8 — Boilers, hot-water plants, and heating distribution critical

Normal-rule anchor

Boiler availability and command do not prove flow, firing, heat transfer, or safe combustion.

Case overlay

Hot-water supply is below target while the lead boiler command is on and pump proof is questionable.

Calculation/evidence callout: Use Q=flow×ΔT×approved fluid factor, reset equations, staging thresholds, and minimum-flow criteria supplied.

Figure 9 — Chillers, cooling towers, and chilled-water plants critical

Normal-rule anchor

Chiller command or run status does not prove correct water flow, capacity, efficiency, or tower operation.

Case overlay

The chiller is at high load while chilled-water ΔT is low and bypass flow is suspected.

Calculation/evidence callout: Calculate tons or heat transfer from supplied flow/ΔT factors, staging load, approach, and plant reset targets.

Figure 10 — Distribution, changeover, and cross-system optimization critical

Normal-rule anchor

Optimized requests and resets are applied only where the approved project sequence makes them applicable and all prerequisite evidence is trustworthy.

Case overlay

A two-pipe building changes to cooling while several heating valves remain open and zone requests persist.

Calculation/evidence callout: Calculate changeover conditions, required hold/purge time, request aggregation, reset limits, and energy-balance reasonableness.