Technical Trade SchoolBAS-500 platform-specialization
BAS-505
Ten concept and evidence figures

BAS-505 Visual Aid Library

Figure-use rule

Each figure is an orientation and reasoning aid, not a project drawing. Learners must pair it with the current sequence, point list, wiring/piping documents, manufacturer instructions, and as-found evidence.

Figure 1 — ABB Cylon ecosystem and engineering architecture critical

Normal-rule anchor

ABB Cylon is a family of related but distinct products; exact model, firmware, tool, module, license, and project architecture control the workflow.

Case overlay

A site has CBV terminals, an FBXi plant controller, FLX I/O, and an INTEGRA supervisor, but the learner cannot identify which project contains the source strategy.

Calculation/evidence callout: Count devices, networks, strategies, I/O, supervisory dependencies, licenses, and unresolved sources of truth.

Figure 2 — Controller-family and hardware selection critical

Normal-rule anchor

A controller that fits physically may still fail the application because of I/O mode, resource, firmware, bus, program, licensing, or lifecycle limits.

Case overlay

A proposed replacement has the right enclosure footprint but insufficient UniPut modes and a different supported firmware path.

Calculation/evidence callout: Reconcile I/O by type, UniPut modes, expansion capacity, program/resource load, network limits, spare capacity, and lifecycle risk.

Figure 3 — CXproHD site, network, controller, strategy, and version model critical

Normal-rule anchor

Saved project, open strategy, live controller, exported archive, and supervisor database can disagree; source-of-truth must be established, not assumed.

Case overlay

A strategy opens under v1.07.06, but the controller firmware and archived .CXB reflect a prior commissioning revision.

Calculation/evidence callout: Compare versions, checksums where available, timestamps, device/strategy counts, missing dependencies, and change coverage.

Figure 4 — Strategy blocks, data types, execution, and readable logic critical

Normal-rule anchor

Block connections do not explain intent; types, units, initialization, execution order, timing, priority, failure, comments, and test vectors must be explicit.

Case overlay

A fan strategy restarts latched on and a timer output reaches a dependent block one execution cycle later than expected.

Calculation/evidence callout: Build truth/state tables, trace several cycles, calculate timing and analog math, and compare predicted with observed strategy values.

Figure 5 — I/O, UniPut, scaling, BACnet priority, and safe failure critical

Normal-rule anchor

UniPut flexibility requires exact mode and electrical verification; a plausible strategy value can still be the wrong signal, priority, or physical state.

Case overlay

An output is configured for the wrong electrical mode while BACnet priority 8 masks the strategy command.

Calculation/evidence callout: Calculate scaling endpoints/midpoint, current/voltage plausibility, effective priority, deviation, proof timeout, and fallback result.

Figure 6 — Terminal and fan-coil strategy centerpiece critical

Normal-rule anchor

Terminal logic must match the actual physical coil, valve, fan, airflow, sensor, changeover, and safety arrangement; a stock example is only a starting hypothesis.

Case overlay

A four-pipe fan coil has three fan speeds, a window contact, condensate alarm, and valves that must not overlap under changeover faults.

Calculation/evidence callout: Calculate deadbands, airflow/temperature scaling, fan thresholds, valve timing, occupancy delays, and changed-case acceptance.

Figure 7 — AHU, plant, VAV, staging, and coordinated applications critical

Normal-rule anchor

Coordination logic cannot hide mechanical design constraints or listed safeties; every request and effective command requires source, limits, proof, fallback, and ownership.

Case overlay

Two pumps alternate weekly, but one fails proof during low-load operation and minimum-flow protection must survive lead substitution.

Calculation/evidence callout: Calculate staging thresholds, run-hour rotation, minimum on/off time, flow/reset values, request persistence, and proof-response limits.

Figure 8 — BACnet/IP, MS/TP, FLX, routing, and addressing critical

Normal-rule anchor

Discovery is incomplete evidence; exact identity, path, electrical topology, object semantics, timing/load, command authority, and process result must agree.

Case overlay

A controller is visible through two routes, an MS/TP MAC is duplicated, and FLX I/O appears but updates intermittently.

Calculation/evidence callout: Reconcile all identities, segment/device load, token/poll timing, latency, error counts, object coverage, and physical response.

Figure 9 — INTEGRA, BuildingPro, graphics, alarms, trends, and tuning critical

Normal-rule anchor

Supervisory objects and ProPack components accelerate engineering but require exact version support, state testing, performance baseline, and physical/process validation.

Case overlay

A ProPack component reports normal while its source point is stale, and a tuning change improves discovery but overloads an older field network.

Calculation/evidence callout: Measure point/binding coverage, history sampling, alarm delivery, schedule precedence, poll/write load, latency, and resource margin.

Figure 10 — Download, debug, firmware, .CXB backup, recovery, and turnover critical

Normal-rule anchor

A project archive is not a proven recovery asset until restored on a compatible isolated target and critical I/O, strategies, networks, supervisory services, users, and operator tasks pass.

Case overlay

A firmware change succeeds but one strategy differs from source and two temporary priorities remain after testing.

Calculation/evidence callout: Reconcile planned/applied/retested items, compare versions/artifacts, calculate RPO/RTO and pass rate, and account for every temporary state and open risk.